Can I switch to wireless control without removing my existing pushbutton wiring?

The receiver relay contact is wired in parallel with the existing button contact; nothing is removed. Interlocks, limits and wired e-stop stay in place.

Yes, you can. The method is simple: the relay contact of the receiver is wired in parallel with the existing pushbutton contact. The same contactor coil is energised whether the button closes or the relay closes; you do not have to remove the existing wiring.

Wiring order

  1. Isolate the panel and note down the existing button cables together with their terminal numbers. Taking a photograph is not enough; write down which end goes where.
  2. Power the receiver. A panel-mount receiver can be powered from 12/24V DC or 220V AC; check first which voltage is available.
  3. Run the relay contact in parallel to the same two points as the contact of the button concerned.
  4. Before switching on, measure every direction by hand, then disconnect the motor and try it with no load.

Points to watch in practice

Where the parallel connection does not fit

The method does not work identically in every panel. In three situations the arrangement changes:

Existing circuitResultWhat to do
Momentary (press-to-run) button circuitA direct parallel connection fitsRun the relay contact in parallel with the button
Latching (start-stop hold-in) circuitThe parallel connection may latch the movement onReview the latching logic, convert it to a momentary arrangement if needed
Button going to a PLC inputIf the contact is paralleled the PLC logic may be bypassedTake the relay to the PLC input and drive the output through the PLC

Whether the relay contact will drive the motor or the coil is settled here as well; connecting the contact directly to the motor is not suitable in most applications.

What to verify during commissioning

Once the wiring is complete, make three trials separately: first with the button alone, then with the remote control alone, and last by pressing both at the same time. The third one is critical; if the contactor chatters when the two commands clash, or opposite directions try to be energised together, it shows the interlocking is incomplete. Trigger the limit switches by hand as well and see that the movement really is cut: a switch that looks to be in series on the diagram may have been bridged out on site. Make the trials with the motor disconnected or with no load, then repeat them at low load.

A phased changeover

This parallel working approach allows a phased changeover, particularly in plants that cannot stop production: the receiver is connected and tested first, then once the site operator has got used to it wireless working becomes the main method and the buttons stay as a backup. On the ST100 and SF100 sets, using the manual button together with the RF remote control is foreseen for this scenario; on other variants confirm the same possibility from the product page. Do not remove the buttons during the changeover and show the operator both methods; the real gain of this approach is that the plant does not stop while the remote control is on charge or when it fails.