What are the rules for making joints inside a junction box or connection box?

A joint should preferably not be made at all; if it is unavoidable it must be made inside an accessible box, with a crimped connection or a terminal. The gland on the cables entering the box must suit the seal diameter, unused holes must be closed with blanking plugs, and a breathing ePTFE plug must be used so that moisture does not build up inside the box. The joint point should give a drop below 0.2 V under load.

Every joint is a new potential fault point. If it is unavoidable, minimise the risk with these rules:

When the job is done, measure the joint point under load: below 0.2 V is good, above 0.5 V is unacceptable.