How do I measure how many amps my motor draws?

Make the measurement with a clamp meter capable of measuring DC current, taking a single conductor of the supply line inside the jaw. Record not the no-load figure but the steady current under real load and the start-up surge. The start-up current is typically 5-8 times the rated current and lasts 0.5-3 seconds.

The steps to follow for a correct measurement:

  1. Use a DC clamp meter. Clamps that measure only AC will not show DC motor current; make sure the instrument measures DC (Hall effect).
  2. Take a single conductor. Take only the positive or only the negative conductor inside the jaw; if you take both together the fields cancel each other and you read zero.
  3. Run it with the real load. Current measured with no load misleads. Move the door, the shutter or the load under normal working conditions.
  4. Record three values: the no-load current, the steady current under load and the start-up surge.
  5. For the start-up surge use the instrument's peak/inrush hold function; the normal averaging mode misses the surge.
  6. Try the worst case: cold weather, tight mechanics, the heaviest load.

The steady value you obtain is the basis of the sizing; the start-up surge, on the other hand, must fit within the driver's peak window. The KS250 carries its 45 A peak value for 5 seconds, the PT500 its 40 A maximum value for 15 seconds. If the measured steady current is approaching 15 A, the PT500's 30 A continuous rating is more suitable.