Voltage Drop

Voltage drop is the number of volts lost before reaching the load end because of the conductor's own resistance. In a DC circuit the outgoing and return conductors are counted together: ΔU = 2·L·I·ρ/A. The loss is directly proportional to current and distance and inversely proportional to cross-section; the lost energy turns into heat.

In the formula L is the one-way distance (m), I the current (A), A the cross-section (mm²), and ρ the resistivity of copper, approximately 0.0175 Ω·mm²/m. Let us make it concrete with an example: if you take a load drawing 20 A over 5 m with 4 mm², ΔU = 2·5·20·0.0175/4 ≈ 0.88 V. If you use 10 mm² on the same run, the loss falls to 0.35 V.

This is usually the source of the field complaint "the device works at the battery, but it is weak when fitted in place". If the voltage at the driver or remote control input is a volt below the voltage at the battery terminals while the motor runs, the cross-section must be increased.

Knowledge Center