Normally Closed Contact (NC)

It is the contact that is closed while the relay or switch is at rest and opens when triggered. NC is preferred on safety and limit lines, because when a cable breaks or the contact fails, the circuit opens by itself and the machine behaves in the direction of stopping.

The safety advantage of the NC contact comes from its failure behaviour. In a closed circuit, a broken conductor, a loose terminal or a burnt contact cuts the current; the system interprets this as a "stop" command. On a limit line built with NO, the same break goes unnoticed and the limit protection is silently disabled.

The typical places for NC in a crane installation are these:

Include NC lines in periodic function testing: if a closed contact fails to open at the moment it should, you will only notice it by triggering it deliberately.