AC-15 Load Category

This is the category defined for switching inductive alternating current control loads such as contactor coils and solenoids. It is the load type the relay output actually faces in a crane panel; the AC-15 capacity of the same contact stays at roughly 15–20% of the AC-1 rating.

Two physical phenomena make AC-15 difficult. The first is pull-in: before the coil has pulled in the air gap is large, so the inductance is low and the current rises to roughly 10 times. The second is interruption: when the current is cut, the magnetic energy stored in the coil is released as an arc across the contact gap.

In the field this corresponds to something clear:

When making a selection, look at the coil data of the contactor you are driving: the pull-in power (VA) and the holding power are given separately; size the contact according to the pull-in value. If you need to drive a motor directly instead of a contactor coil, do not forget that it is the motor's current characteristic and not the relay output that is decisive.