0–10 V Analog Input

It is the common analog reference standard in industrial automation; 0 V corresponds to the zero command and 10 V to full command. Thanks to the wide voltage span, the same absolute noise level causes half as much error as it would on a 0–5 V input. The source impedance must be kept low and the signal carried in shielded cable.

0–10 V is the standard output of PLC analog output cards and panel-mounted speed setting units. On the driver side this voltage is usually reduced by a resistor divider into the 0–3.3 V or 0–5 V band the microcontroller can read.

If broken-line detection matters over long distances, a 4–20 mA loop is more suitable. On the KS250, IN5 and on the PT500, input E are defined as the analog reference input; since the product data does not state the voltage range these inputs accept, verify from the connection diagram whether scaling is needed before connecting a 0–10 V source.